Field-Oriented Control Induction Motor Drive
Implement field-oriented control (FOC) induction motor drive model
Description
The Field-Oriented Control Induction Motor Drive block represents a standard vector or rotor field-oriented control drive for induction motors. This drive features closed-loop speed control based on the indirect or feedforward vector control method. The speed control loop outputs the reference electromagnetic torque and rotor flux of the machine. The reference direct and quadrature (dq) components of the stator current, corresponding to the commanded rotor flux and torque, are derived based on the indirect vector control strategy. The reference dq components of the stator current are then used to obtain the required gate signals for the inverter through a hysteresis-band or PWM current controller.
The main advantage of this drive compared to scalar-controlled drives is its fast dynamic response. The inherent coupling effect between the torque and flux in the machine is managed through decoupling (rotor flux orientation) control, which allows the torque and flux to be controlled independently. However, due to its computation complexity, the implementation of this drive requires fast computing processors or DSPs.
Note
In Simscape™
Electrical™ Specialized Power Systems software, the Field-Oriented Control Induction
Motor Drive block is commonly called the AC3
motor drive.
The Field-Oriented Control Induction Motor Drive block uses these blocks from the Electric Drives / Fundamental Drive Blocks library:
Speed Controller (AC)
Field-Oriented Controller
DC Bus
Inverter (Three-Phase)
Remarks
The model is discrete. Good simulation results have been obtained with a 2 µs time step. To simulate a digital controller device, the control system has two different sampling times:
Speed controller sampling time
FOC sampling time
The speed controller sampling time has to be a multiple of the FOC sampling time. The latter sampling time has to be a multiple of the simulation time step. The average-value inverter allows the use of bigger simulation time steps since it does not generate small time constants (due to the RC snubbers) inherent to the detailed converter. For an FOC sampling time of 60 µs, good simulation results have been obtained for a simulation time step of 60 µs. This time step cannot be higher than the FOC time step.
Parameters
General
- Output bus mode
Select how the output variables are organized. If you select
Multiple output buses
(default), the block has three separate output buses for motor, converter, and controller variables. If you selectSingle output bus
, all variables output on a single bus.- Model detail level
Select between the detailed and the average-value inverter. Default is
Detailed
.- Mechanical input
Select between the load torque, the motor speed and the mechanical rotational port as mechanical input. Default is
Torque Tm
.If you select and apply a load torque, the output is the motor speed according to the following differential equation that describes the mechanical system dynamics:
This mechanical system is included in the motor model.
If you select the motor speed as mechanical input, then you get the electromagnetic torque as output, allowing you to represent externally the mechanical system dynamics. The internal mechanical system is not used with this mechanical input selection and the inertia and viscous friction parameters are not displayed.
For the mechanical rotational port, the connection port S counts for the mechanical input and output. It allows a direct connection to the Simscape environment. The mechanical system of the motor is also included in the drive and is based on the same differential equation.
- Use bus as labels
When you select this check box, the
Motor
,Conv
, andCtrl
measurement outputs use the signal names to identify the bus labels. Select this option for applications that require bus signal labels to have only alphanumeric characters.When this check box is cleared (default), the measurement output uses the signal definition to identify the bus labels. The labels contain nonalphanumeric characters that are incompatible with some Simulink® applications.
- Set sensorless
When you select this check box, the motor speed is estimated from terminal voltages and currents based on the Model Referencing Adaptive System (MRAS) technique. The Sensorless tab contains the estimator controller parameters.
When this check box is cleared, the motor speed is measured by an internal speed sensor, and the Sensorless tab is not displayed on the block mask.
Asynchronous Machine Tab
The Asynchronous Machine tab displays the parameters of the Asynchronous Machine block of the Fundamental Blocks (powerlib) library.
Converters and DC Bus Tab
The Rectifier section of the Converters and DC Bus tab displays the parameters of the Universal Bridge block of the Fundamental Blocks (powerlib) library. For more information on the universal bridge parameters, refer to the Universal Bridge reference page.
- Capacitance
The DC bus capacitance (F). Default is
2000e-6
.
- Resistance
The braking chopper resistance used to avoid bus over-voltage during motor deceleration or when the load torque tends to accelerate the motor (ohms). Default is
8
.- Chopper frequency
The braking chopper frequency (Hz). Default is
4000
.- Activation voltage
The dynamic braking is activated when the bus voltage reaches the upper limit of the hysteresis band (V). The following figure illustrates the braking chopper hysteresis logic. Default is
320
.- Shutdown voltage
The dynamic braking is shut down when the bus voltage reaches the lower limit of the hysteresis band (V). The Chopper hysteresis logic is shown in the next figure. Default is
310
.
The Inverter section of the Converters and DC Bus tab displays the parameters of the Universal Bridge block of the Fundamental Blocks (powerlib) library. For more information on the universal bridge parameters, refer to the Universal Bridge reference page.
The average-value inverter uses the following parameters.
- Source frequency
The frequency of the three-phase voltage source (Hz). Default is
60
.- On-state resistance
The on-state resistance of the inverter switches (ohms). Default is
1e-3
.
Controller Tab
- Regulation Type
This pop-up menu allows you to choose between speed and torque regulation. Default is
Speed regulation
.- Modulation type
Select hysteresis or space vector modulation. The default modulation type is
Hysteresis
.- Schematic
When you click this button, a diagram illustrating the speed and current controllers schematics appears.
- Speed Ramps — Acceleration
The maximum change of speed allowed during motor acceleration (rpm/s). An excessively large positive value can cause DC bus under-voltage. This parameter is used in speed regulation mode only. Default is
900
.- Speed Ramps — Deceleration
The maximum change of speed allowed during motor deceleration (rpm/s). An excessively large negative value can cause DC bus overvoltage. This parameter is used in speed regulation mode only. Default is
-900
.- Speed cutoff frequency
The speed measurement first-order low-pass filter cutoff frequency (Hz). This parameter is used in speed regulation mode only. Default is
1000
.- Speed controller sampling time
The speed controller sampling time (s). The sampling time must be a multiple of the simulation time step. Default is
100e-6
.- PI regulator — Proportional gain
The speed controller proportional gain. This parameter is used in speed regulation mode only. Default is
300
.- PI regulator — Integral gain
The speed controller integral gain. This parameter is used in speed regulation mode only. Default is
2000
.- Torque output limits — Negative
The maximum negative demanded torque applied to the motor by the current controller (N.m). Default is
-1200
.- Torque output limits — Positive
The maximum positive demanded torque applied to the motor by the current controller (N.m). Default is
1200
.
- Flux Controller — Proportional gain
The flux controller proportional gain. Default is
100
.- Flux Controller — Integral gain
The flux controller integral gain. Default is
30
.- Flux output limits — Negative
The flux controller maximum negative output (Wb). Default is
-2
.- Flux output limits — Positive
The flux controller maximum positive output (Wb). Default is
2
.- Lowpass filter cutoff frequency
The flux estimation first-order filter cutoff frequency (Hz). Default is
16
.- Sampling Time
The FOC controller sampling time (s). The sampling time must be a multiple of the simulation time step. Default is
20e-6
.- Current controller hysteresis band
The current hysteresis bandwidth. This value is the total bandwidth distributed symmetrically around the current set point (A). Default is
10
. The following figure illustrates a case where the current set point is Is*and the current hysteresis bandwidth is set to dx.This parameter is not used when using the average-value inverter.
- Maximum switching frequency
The maximum inverter switching frequency (Hz). This parameter is not used when using the average-value inverter. Default is
20000
.- Show/Hide Autotuning Control
Select to show or hide the parameters of the Autotuning Control tool.
- Desired damping [zeta]
Specify the damping factor used for the calculation of the Kp and Ki gains of the Speed Controller (AC) block. Default is
0.9
.- Desired response time @ 5% [Trd (sec)]
Specify the desired settling time of the Speed Controller (AC) block. This is time required for the controller response to reach and stay within a 5 percent range of the target value. Default is
0.1
.- Bandwidth ratio (InnerLoop/SpeedLoop)
Specify the ratio between the bandwidth and natural frequency of the regulator. Default is
30
.- Calculate PI regulator gains
Compute the Proportional gain and Integral gain parameters of the Speed Controller (AC) and of the Field-Oriented Controller blocks. The computation is based on the Desired damping [zeta], Desired response time @ 5%, and Bandwidth ratio (InnerLoop/SpeedLoop) parameters. The computed values are displayed in the mask of the Drive block. Click Apply or OK to confirm them.
Sensorless Tab
- Proportional gain
Specify the value of the proportional gain of the PI regulator that is used to tune the motor speed.
Default is
5000
.- Integral gain
Specify the value of the integral gain of the PI regulator that is used to tune the motor speed.
Default is
50
.- Upper - Upper output limit
Specify the upper output limit of the PI controller.
Default is
500
.- Lower - Lower output limit
Specify the lower output limit of the PI controller.
Default is
-500
.- Controller sample time
Controller sample time, in s. The sample time must be a multiple of the simulation time step. Default is
2e-06
.
Block Inputs and Outputs
SP
The speed or torque set point. The speed set point can be a step function, but the speed change rate will follow the acceleration / deceleration ramps. If the load torque and the speed have opposite signs, the accelerating torque will be the sum of the electromagnetic and load torques.
Tm
orWm
The mechanical input: load torque (Tm) or motor speed (Wm). For the mechanical rotational port (S), this input is deleted.
A, B, C
The three phase terminals of the motor drive.
Wm
,Te
orS
The mechanical output: motor speed (Wm), electromagnetic torque (Te) or mechanical rotational port (S).
When the Output bus mode parameter is set to Multiple output buses, the block has the following three output buses:
Motor
The motor measurement vector. This vector allows you to observe the motor's variables using the Bus Selector block.
Conv
The three-phase converters measurement vector. This vector contains:
The DC bus voltage
The rectifier output current
The inverter input current
Note that all current and voltage values of the bridges can be visualized with the Multimeter block.
Ctrl
The controller measurement vector. This vector contains:
The torque reference
The speed error (difference between the speed reference ramp and actual speed)
The speed reference ramp or torque reference
When the Output bus mode parameter is set to Single output bus, the block groups the Motor, Conv, and Ctrl outputs into a single bus output.
Model Specifications
The library contains a 3 hp and a 200-hp drive parameter set. The specifications of these two drives are shown in the following table.
3 HP and 200 HP Drive Specifications
3 HP Drive | 200 HP Drive | ||
---|---|---|---|
Drive Input Voltage | |||
Amplitude | 220 V | 460 V | |
Frequency | 60 Hz | 60 Hz | |
Motor Nominal Values | |||
Power | 3 hp | 200 hp | |
Speed | 1705 rpm | 1785 rpm | |
Voltage | 220 V | 460 V |
Examples
The ac3_example
example illustrates an AC3 motor drive simulation
with standard load conditions for the detailed and average-value models.
References
[1] Bose, B. K. Modern Power Electronics and AC Drives. Upper Saddle River, NJ: Prentice-Hall, 2002.
[2] Grelet, G., and G. Clerc. Actionneurs électriques. Paris: Éditions Eyrolles, 1997.
[3] Krause, P. C. Analysis of Electric Machinery. New York: McGraw-Hill, 1986.
Version History
Introduced in R2006a